PK4-DB four-button DALI-2 wall panel, grey face, blue indicators
PK4-DB front, four buttons in two rows
PK4-DB rear, DALI terminals DA1 and DA2, bus powered
  • New
PK4-DB four-button DALI-2 wall panel, grey face, blue indicators
PK4-DB front, four buttons in two rows
PK4-DB rear, DALI terminals DA1 and DA2, bus powered

PK4-DB 4-Button DALI-2 Wall Panel

Four-button DALI-2 wall panel. It draws 10 mA from the DALI bus and reports each button to IEC 62386-301. It does not drive a lamp. It needs a DALI-2 application controller that reads push-button inputs, and a bus supply when that controller does not feed the line.

HL-PK4-DB

Need more than we have in stock?

We have 5 in stock, ready to dispatch. If you need more, increase the quantity and add it to the basket. Extra units go on back order: we will use incoming stock if any is still free, otherwise delivery is typically 30–45 days.
5 Items In stock
Next working day delivery
£42.00
(£
50.40
with VAT)
VAT excluded

Tags:
 

HL-PK4-DB is the four-button panel. It provides four instances of type 1. The buttons sit in two rows. HL-PK8-DB is the same panel with eight buttons.

What it does. This is a DALI-2 input device. Each button is one push-button instance to IEC 62386-301. A press sends an event on the bus. An application controller reads that event and then commands the drivers. This panel does not drive a lamp, it has no relay, and it does not send a dimming level of its own.

What has to be on the bus. A DALI-2 application controller that reads IEC 62386-301 push-button instances. The address, the scenes and the action of each button are set in that controller, often through its USB interface. HL-DA-M(WT), HL-DA-ML(WT) and HL-TPS-D-WT send commands to DALI control gear. They do not read these button events, so they are not the controller for this panel.

Power. The panel is powered only from the DALI bus. Current draw is 10 mA at 16 V. The pair is polarity-free. Two terminal pairs, both marked DA1 and DA2, loop the bus in and out. Use 0.5 to 2.0 mm2 cable, stripped 4 to 5 mm. Do not put mains on these terminals.

Bus supply. If the application controller already feeds the bus, a second supply is not added. If it does not, use one bus supply for the line. HL-DA-PS is 200 mA at 16 V. This panel uses 10 mA of that. HL-DA-ER, the ceiling sensor, uses about 8 mA. Every other device on the line reduces what is left. The manual does not state a maximum number of panels.

Buttons. Several panels can share one DALI line. Each button can report a press, a release, a short press, a double press, a long press and a stuck button. The timings are set in the application controller under IEC 62386-301.

Blue indicators. Each button has a blue indicator. Feedback to IEC 62386-332 needs an application controller that supports that part. At rest the indicator is dimly lit. It is brighter when the system is commanded on, and dim again on an off command.

Stickers. The pack has 64 transparent stickers, including on, off, scene, brightness and colour temperature. A sticker names the button. It does not program it.

Fit. The face is 86 x 86 mm, for a European 86 wall box. The rear housing is 60 x 52 mm. Overall depth is 35.5 mm. Take the face off, fix the base, and fit the face back on. Dry rooms only. The body is IP20. Ambient -20 to +55 C. Case up to 65 C. The carton is 112 x 112 x 50 mm. Gross weight 0.169 kg.

Marks. The manual lists EN 61347-1, EN 61347-2, EN IEC 55015, EN IEC 61547 and ETSI EN 301 489-1/-3, and marks the unit DALI-2, CE and RoHS. Warranty 5 years.

Brand
Hi-Line
IP Rating
IP20 (Non-waterproof)
Type
DALI-2 input
Type of control
DALI
Warranty
5 Years
No reviews